Valve Body (less orifice)
BOC Part No. | Refrigerant | Pressure equaliser | Application | Danfoss Code No. |
TX2 | R22 | Internal | Range ‘N’ -40° to 10°C | 068Z3206 |
TEX2 | R22 | External | Range ‘N’ -40° to 10°C | 068Z3209 |
TN2 | R134a | Internal | Range ‘N’ -40° to 10°C | 068Z3346 |
TEN2 | R134a | External | Range ‘N’ -40° to 10°C | 068Z3348 |
TS2 | R507 / R404A | Internal | Range ‘N’ -40° to 10°C | 068Z3400 |
TES2 | R507 / R404A | External | Range ‘N’ -40° to 10°C | 068Z3403 |
TS2MOP | R507 / R404A | Internal | Range ‘NL’ -40° to 15°C | 068Z3408 |
TES2MOP | R507 / R404A | External | Range ‘NL’ -40° to 15°C | 068Z3409 |
Orifice (with strainer and capillary tube label)
BOC Part No. | Orifice number | Rated capacity* (kW) | Danfoss Code No. | |||
R22 | R134a | R404A | R407C | |||
T20X | 0X | 0.5 | 0.4 | 0.38 | 0.5 | 068-2002 |
T200 | 00 | 1.0 | 0.9 | 0.7 | 1.1 | 068-2003 |
T201 | 01 | 2.5 | 1.8 | 1.6 | 2.7 | 068-2010 |
T202 | 02 | 3.5 | 2.6 | 2.1 | 3.8 | 068-2015 |
T203 | 03 | 5.2 | 4.6 | 4.2 | 5.6 | 068-2006 |
T204 | 04 | 8.0 | 6.7 | 6.0 | 8.6 | 068-2007 |
T205 | 05 | 10.5 | 8.6 | 7.7 | 11.3 | 068-2008 |
T206 | 06 | 15.5 | 10.5 | 9.1 | 16.7 | 068-2009 |