BOC Part No. | Type | Danfoss Code No. | Connection | Opening diff. pressure | Temp. of medium (°C) | Max working press. (kPa) | kV factor (m3/h) | ||
Min. | Max. (liquid)² | ||||||||
AC. | DC. | ||||||||
EVR3 | EVR3 | 032F1205 | 1/4" flare | 0 | 2100 | 1800 | -40 to 100 | 3500 | 0.27 |
EVR3S | EVR3 | 032F1206 | 1/4" solder | 0 | 2100 | 1800 | -40 to 100 | 3500 | 0.27 |
EVR6 | EVR6 | 032F1211 | 3/8" flare | 5 | 2100 | 1800 | -40 to 105 | 3500 | 0.8 |
EVR6S | EVR6 | 032F1212 | 3/8" solder | 5 | 2100 | 1800 | -40 to 105 | 3500 | 0.8 |
EVR10 | EVR10 | 032F1215 | 1/2" flare | 5 | 2100 | 1800 | -40 to 105 | 3500 | 1.9 |
EVR10S | EVR10 | 032F1217 | 1/2" solder | 5 | 2100 | 1800 | -40 to 105 | 3500 | 1.9 |
EVR15 | EVR15 | 032F1220 | 5/8" flare | 5 | 2100 | 1800 | -40 to 105 | 3500 | 2.6 |
EVR15S | EVR15 | 032F1228 | 5/8" solder | 5 | 2100 | 1800 | -40 to 105 | 3500 | 2.6 |
EVR20S | EVR20 | 032F1240 | 7/8" flare | 5 | 2100 | 1800 | -40 to 105 | 3500 | 5.0 |
EVR25S | EVR25 | 032F2201 | 1 1/8" sold | 5 | 2100 | 1800 | -40 to 105 | 3500 | 10.0 |
- The rated liquid and suction vapour capacities are based on an evaporating temperature te = -10°C, liquid temperature ahead of the valve tl = +25°C and a pressure drop across the valve p = 0, 15 bar. The rated hot gas capacity is based on a condensing temperature tc = 40°C, pressure drop across the valve p = 0.8 bar and hot gas temperature th = 65°C.
- MOPD for media in gas form is approx. 1 bar greater
- kv - factor is the water flow in m3/h at a pressure drop across the valve of 1 bar, p = 1000 kg/m³.
Type | Rated capacity (kW) | |||||
Liquid line | Suction line | Hot gas line | ||||
R 134a | R 404A | R 134a | R 404A | R 134a | R 404A | |
EVR3 | 5.0 | 3.9 | 2.0 | 2.0 | ||
EVR6 | 14.9 | 11.8 | 1.4 | 1.6 | 5.8 | 6.2 |
EVR10 | 35.3 | 27.9 | 3.2 | 3.9 | 13.9 | 14.8 |
EVR15 | 48.3 | 36.5 | 4.4 | 5.2 | 19.0 | 20.1 |
EVR20 | 92.8 | 73.2 | 8.5 | 10.2 | 36.5 | 35.7 |
EVR25 | 186.0 | 141.0 | 17.0 | 20.3 | 73.0 | 78.1 |